Skip to content

Ft pt1

Type Function module

Input IN REAL (input signal)
T TIME (time constant)
K REAL (multiplier)
Output OUT_MAX REAL (upper output limit)
FT_PT1 is an LZI- Transmission link with a proportional transfer behavior 1 Order, even as a low pass filter 1 order referred to. The multiplier K sets the gain (multiplier) is fixed and T is the time constant. A change at the input is attenuated at the output visible. The output signal increases within T to 63% of the input value and after 3 * T to 95% of input values. Thus, after an abrupt change of the input signal of 0 to 10 at the time of the initial input change 0, increasing to 1 at T * 6.3 and after 3 * T 9.5 and then approaches asymptotically the value 10. The first time the output OUT to the IN input value is initialized to a defined starting performance guarantee. If the input T of T#0s is equal to the output OUT = K * IN.

| Structure diagram | | | | Step response for T = 1, K = 1 |

ft_pt1

ft_pt1_diag ft_pt1_diag2