Input IN REAL (input signal)
T TIME (time constant)
K REAL (multiplier)
Output OUT REAL (High pass with time constant T )
FT_IMP is a high-pass filter with time constant T and multiplier K. An abrupt change at the input is visible at the output, but after the time T the value is already smoother by 63% and after 3 * T by 95%. Thus, after an abrupt change of the input signal from 0 to 10, the output passes 10 at the beginning and reduces after 1* T to 3.7 and after 3 * T to 0.5 and then gradually to 0.