Dead band
DEAD_BAND¶
| Type | Function |
| Input X | REAL (input) |
| L | REAL ( Lockout Value) |
| Output | REAL (output value) |
| DEAD_BAND is a linear transfer function with dead zone. The function moves the positive part of the curve to -L and the negative part of the curve by +L. DEAD_BAND is used to filter a quantization noise and other noise components from a signal. DEAD_BAND, for example, is used in control systems in order to prevent that the controller permanently switches in small increments, while the actuator is overstressed and worn out. | |
| DEAD_BAND = X - SGN(X)*L if ABS(X)> L if ABS(X) > L | |
| DEAD_BAND = 0 if ABS(X) <= L |