NET_VAR_CONTROL

Type Function module
IN_OUT X NET_VAR_DATA (NET_VAR data structure)
INPUT ACTIVATE BOOL (Enables the exchange of data)
MASTER BOOL (FALSE = SLAVE / MASTER = TRUE)
UDP BOOL (FALSE=TCP / TRUE = UDP)
REMOTE_IP4 DWORD (IP4-address of the other SPS)
REMOTE_PORT WORD (PORT number of other PLC)
SCAN_TIME TIME (update time)
WATCHDOG TIME (monitoring time)
OUTPUT RUN BOOL (active data exchange - no error)
ERROR DWORD ((error code)
The module NET_VAR_CONTROL coordinates the data exchange between the two controllers and the satellite components NET_VAR_*. With ACTIVATE = TRUE, the data exchange will be released. The module must be invoked on both controllers, with the parameter MASTER must be assigned once with TRUE and once must be FALSE. Thus determines which side the active connection will establish. With UDP (FALSE / TRUE) can be specified whether a UDP or TCP connection is used. The the IP address of the other side must be specified in REMOTE-IP4, and alternatively, the port address (default port is 10000). The SCAN TIME determines a data refresh interval (default is T # 1s). WIth WATCHDOG the monitoring time is set (default is T # 2s). When data exchange runs, the parameter RUN = TRUE. If the data exchange is longer than the watchdog time not possible, RUN = FALSE and an error is passed. The error will not be acknowledged, because the module automatically tries to restore the data exchange. Once no more error exists, RUN = TRUE and the error code is cleared.
ERROR (regarded as a HEX value!)

net_var_control

DWORD Message Type Description
B3 B2 B1
XX .. ..
.. XX ..
.. .. XX
.. .. ..