Skip to content

Sys log

SYS_LOG

Type Function module
IN_OUT IP_C IP_C (parameterization)
S_BUF NETWORK_BUFFER (transmit data)
R_BUF NETWORK_BUFFER (receive data)
INPUT ACTIVATE BOOL (positive edge starts the query)
LDT DT (local time)
SERVER_IP4 DWORD (IP address of the syslog server)
PORT WORD (Port number of the syslog server)
FACILITY BYTE (specifies the service or component)
SEVERITY BYTE (Classification of severity)
TAG STRING(32) (Process name, ID, etc.)
HOST NAME STRING (Name or IP address of the sender)
MESSAGE STRING(string_length) (Message)
OPTION BYTE (Various )
OUTPUT DONE BOOL (Query completed without errors)
ERROR DWORD (Error code)
SYSLOG is a standard for transmitting messages in an IP computer network. The protocol is very simple - the client sends a short text message to the syslog receiver. The receiver is also called "syslog daemon" or "syslog server". The messages are sent using UDP port 514 or TCP port 1468 and includes the message in plain text. SYSLOG is typical used for computer systems management and security surveillance. This enables the easy integration of various log sources to a central syslog server. The server software is available for all platforms, sometimes known as free / shareware. Unix or Linux systems have a syslog server already integrated. Through a positive edge at ACTIVATE from the parameters of LDT, FACILITY, SEVERITY, TAG, HOST NAME, MESSAGE a syslog message is generated and sent to the SERVER_IP4 mail address. With OPTION various properties can still be controlled (See Table OPTION). After successfully sending DONE gets TRUE, otherwise ERROR is issued when the actual error message (See ERROR of module IP_CONTROL).
FACILITY,SEVERITY,TIMESTAMP,HOSTNAME,TAG,MESSAGE

sys_log sys_log_schema

Example:

Example:

MAIL.ERR: Sep 10 08:31:10 149.100.100.02 PLANT2_PLC1 This is a test message generated by OSCAT SYSLOG

The following options can be used

Severity is defined as the following standard:

The following facility is defined as standard:

For general syslog messages, the facility values 16-23 are provided (local0 to local7). But it is quite permissible to use the predefined values from 0 to 15 for own purposes.

With Facility and Severity can be filtered on the SYSLOG server (database) according to certain reports, such as: "Record all error messages from the mail server with severity level.

Example (screenshot) of a syslog server for Windows

BIT Function
0 FALSE = with Facility, Severity codeTRUE = No Facility, Severity code
1 FALSE = with RFC headerTRUE = without RFC Header (only the MESSAGE alone sent)
2 FALSE = with CR,LF at endTRUE = without CR,LF end
3 FALSE = UDP ModusTRUE = TCP Modus
Severity Description
0 Emergency
1 Alert
2 Critical
3 Error
4 Warning
5 Notice
6 Informational
7 Debug
Facility Description
00 Kernel message
01 user-level messages
02 mail system
03 system daemons
04 security/authorization messages
05 messages generated internally by syslogd
06 line printer subsystem
07 network news subsystem
08 UUCP subsystem
09 clock daemon
10 security/authorization messages
11 FTP daemon
12 NTP subsystem
13 log audit
14 log alert
15 clock daemon
16 local10
17 local11
18 local12
19 local13
20 local14
21 local15
22 local16
23 local17